Unless explicitly specified otherwise, the following technical specifications are valid for all components of the SINAMICS S120 booksize drive system.
Note:
When engineering the complete SINAMICS S120 drive, the system data of the associated Control Units, supplementary system components, DC link components and Sensor Modules must be taken into consideration.
Electrical specifications |
|||
Line voltage |
380 ... 480 V 3 AC ±10 % (-15 % <1 min) |
||
Line system configurations |
Grounded TN/TT systems and non-grounded IT systems |
||
Line frequency |
47 ... 63 Hz |
||
Electronics power supply |
24 V DC -15 %/+20 %1), safety extra low-voltage (PELV/SELV) |
||
Short-circuit current rating (SCCR) (Short Circuit Current Rating) |
1.1 ... 447 kW: 65 kA |
||
Electromagnetic compatibility According to EN 61800‑3 |
Second environment, Category C2/C3 For further information, see section Configuration notes |
||
Overvoltage category According to IEC/EN 61800‑5‑1 |
III |
||
Mechanical specifications |
|||
Degree of protection |
|
||
|
IP20 |
||
|
Open type |
||
Protection class |
|
||
|
I |
||
|
Safety extra low-voltage PELV/SELV |
||
Ambient conditions |
|||
|
Storage |
Transport |
Operation |
In product packaging |
In transport packaging |
|
|
Climatic environmental conditions |
Class 1K4 |
Class 2K4 |
Class 3K3 3) Relative humidity 5 ... 95 % |
Environmental class/harmful chemical substances |
Class 1C2 |
Class 2C2 |
Class 3C2 |
Organic/biological influences |
Class 1B1 |
Class 2B1 |
Class 3B1 |
Pollution degree 2) acc. to IEC/EN 61800‑5‑1 |
2 |
||
Installation altitude |
|
||
|
Without derating |
||
|
|
||
|
|
||
|
and additionally:
|
||
|
|
||
Mechanical strength |
|||
|
Storage |
Transport |
Operation |
In product packaging |
In transport packaging |
|
|
Vibratory load |
Class 1M2 |
Class 2M3 |
Class 3M1 |
Shock load |
Class 1M2 |
Class 2M3 |
Class 3M1 |
Certificates |
|||
Declarations of conformity |
CE (Low Voltage, EMC and Machinery Directive) |
||
Certificates of suitability |
cULus |
1) When using a motor holding brake, restricted voltage tolerances (24 V ±10 %) might need to be taken into account.
2) The components must be protected against conductive pollution, e.g. by installing them in a control cabinet with degree of protection IP54 according to IEC 60529 or NEMA 12. If conductive pollution can be excluded at the installation site, a lower degree of cabinet protection is permissible.
3) Better than 3K3 through increased ruggedness regarding the temperature range and humidity. Oil mist, salt mist, ice formation, condensation, dripping water, spraying water, splashing water and water jets are not permitted.
4) Also carefully observe the permissible temperatures for the Control Unit and operator panel.
The Active Interface Modules combine with the Active Line Modules to form a functional unit and are required for operation of the associated Active Line Module. The Active Interface Modules contain a Clean Power Filter and basic interference suppression to ensure compliance with Category C3 in accordance with EN 61800-3 with respect to emitted interference.
The Clean Power Filter protects the mains connection from switching-frequency harmonics. The drive system therefore draws a sinusoidal current from the supply and causes almost no harmonics.
The Active Line Modules in combination with the Active Interface Module can also be operated with supply systems with an isolated star point (IT supply systems).
The scope of supply of the Active Interface Modules includes:
- Connector X21 for temperature evaluation and fan controlConnection example for Active Interface Module
The Active Interface Module requires a 24 V DC supply for operation of the integral fan.
The fan rotates after the 24 V DC supply is applied and can, if necessary (service life, noise), be disconnected from the Control Unit over the "Fan off" input. It is only permitted to switch off the fan when the infeed of the drive system is not operating, otherwise the Active Interface Module will overheat.
The thermostatic switch installed in the Active Interface Module is evaluated over the connected Active Line Module.
The power cables between the Active Interface Module and Active Line Module must be shielded if limit values for interference suppression are to be complied with. The cable shield can be routed over the shield connection plate (option) to the Active Interface Module or Active Line Module.
Depending on the position of the Active Interface Module in the drive system, additional DRIVE-CLiQ cables may be required. If it is separately installed next to the left side of the Control Unit and Active Line Module, no additional DRIVE-CLiQ cables are required. If the Active Interface Module is placed between the Control Unit and Active Line Module, the DRIVE-CLiQ cables supplied with the Active Line Modules are suitable for setting up a line topology, i.e. Active Line Module and all Motor Modules in series on one DRIVE-CLiQ line. If the Active Line Module is connected over a separate DRIVE-CLiQ line, the DRIVE-CLiQ cable marked with (1) must be ordered. A DRIVE-CLiQ cable suitable for connection (2) is included in the scope of supply of the Active Line Module.
For DRIVE-CLiQ cables for different configurations, see section MOTION-CONNECT connection systems.
Separate Active Interface Module
Active Interface Module integrated in the drive line-up
Line voltage 380 ... 480 V 3 AC |
Active Interface Module |
|||||
---|---|---|---|---|---|---|
Internal air cooling |
6SL3100-0BE21-6AB0 |
6SL3100-0BE23-6AB0 |
6SL3100-0BE25-5AB0 |
6SL3100-0BE28-0AB0 |
6SL3100-0BE31-2AB0 |
|
Rated current |
A |
26 |
58 |
88 |
128 |
192 |
Current requirement 24 V DC electronics power supply, max. |
A |
0.25 |
0.49 |
0.6 |
1.2 |
1.2 |
Internal resistance Digital input |
Ω |
1440 ±10 % |
1440 ±10 % |
1440 ±10 % |
1440 ±10 % |
1440 ±10 % |
Power loss |
kW |
0.27 |
0.34 |
0.38 |
0.49 |
0.585 |
Cooling air requirement |
m3/s (ft3/s) |
0.03 (1.1) |
0.04 (1.4) |
0.083 (2.9) |
0.167 (5.9) |
0.167 (5.9) |
Sound pressure level LpA (1 m) |
dB |
57 |
60 |
66 |
68 |
68 |
Line supply/load connection L1, L2, L3/U2, V2, W2 |
|
Connector |
Screw terminals |
Screw terminals |
M8 screw studs |
M8 screw studs |
|
mm2 |
16 |
50 |
50 |
2.5 … 120 or 2 × 50 |
2.5 … 120 or 2 × 50 |
Thermostatic switch (NC contact) |
|
|
|
|
|
|
|
|
250 V AC/1.6 A |
250 V AC/1.6 A |
250 V AC/1.6 A |
250 V AC/1.6 A |
250 V AC/1.6 A |
PE connection |
|
M5 screw |
M6 screw |
M6 screw |
M8 screw |
M8 screw |
Degree of protection |
|
IP20 |
IP20 |
IP20 |
IP20 |
IP20 |
Dimensions |
|
|
|
|
|
|
|
mm (in) |
100 (3.94) |
150 (5.91) |
200 (7.87) |
300 (11.81) |
300 (11.81) |
|
mm (in) |
380 (14.96) |
380 (14.96) |
380 (14.96) |
380 (14.96) |
380 (14.96) |
|
mm (in) |
270 (10.63) |
270 (10.63) |
270 (10.63) |
270 (10.63) |
270 (10.63) |
Weight, approx. |
kg (lb) |
11.6 (25.6) |
19 (41.9) |
23.2 (51.2) |
31.9 (70.3) |
36.6 (80.7) |
Certificate of suitability |
|
cURus |
cURus |
cURus |
cURus |
cURus |
Suitable for Active Line Module in booksize format |
Type |
6SL3130-7TE21-6AA4 |
6SL3130-7TE23-6AA3 |
6SL3130-7TE25-5AA3 |
6SL3130-7TE28-0AA3 |
6SL3130-7TE31-2AA3 |
|
kW (hp) |
16 (18) |
36 (40) |
55 (60) |
80 (100) |
120 (150) |
Duty cycle with previous load
S6 duty cycle with previous load
S6 duty cycle with previous load
55 kW Active Line Module only:
Peak power load duty cycle with previous load
Output power as a function of ambient temperature
Installation altitude
- >1000 ... 4000 m (3281 ... 13124 ft) above sea level